12
TROUBLESHOOTING
12.3 Error Code List
12.3.3 Error code list (1000 to 1999)
12 - 85
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
1436
The error of the Multiple CPU high
speed main base unit is detected. (An
error of the multiple CPU high speed
transmission was detected.)
Reset the CPU module and RUN it
again. If the same error is displayed
again, the CPU module has hardware
failure. (Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
QnU
*10
1437
Take noise reduction measures.
Check the main base unit mounting
status of the CPU module.
Reset the CPU module and RUN it
again. If the same error is displayed
again, the CPU module has hardware
failure. (Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
1439
An error of the multiple CPU high speed
main base unit was detected. (An error
of the multiple CPU high speed
transmission was detected.)
Reset the CPU module and Run it
again. If the same error is displayed
again, the CPU module has hardware
failure. (Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
1500
A momentary power supply
interruption has occurred.
The power supply went off.
Check the power supply.
Rem
1510
The power supply voltage (100 to
240VAC) of either of the two power
supply modules on the power supply
duplexing extension base unit dropped
to or below 85% of the rated voltage.
(This can be detected from the control
system of the redundant system.)
Check the supply voltage of the power
supply module. If the voltage is
abnormal then replace the power supply
module.
Q4AR
The power supply voltage of either of
redundant power supply modules on
the redundant base unit dropped.
Check the power supplied to the
redundant power supply modules
mounted on the redundant base unit.
Qn(H)
*6
QnPH
*6
QnPRH
QnU
*13
Rem
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 Function version is B or later.
*5 Function version is A.
*6 The module whose first 5 digits of serial No. is 04101 or later.
*7 The module whose first 5 digits of serial No. is 07032 or later.
*8 The module whose first 5 digits of serial No. is 08032 or later.
*9 The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.
*11 The Q13UDHCPU and Q26UDHCPU
*12 This applies to the QnUDE(H)CPU.
*13 The module whose first 5 digits of serial No. is 10042 or later.