EasyManua.ls Logo

Mitsubishi Q01CPU - Page 439

Mitsubishi Q01CPU
732 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
TROUBLESHOOTING
12.3 Error Code List
12.3.4 Error code list (2000 to 2999)
12 - 115
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
2125
A module which the QCPU cannot
recognise has been installed.
There was no response form the
intelligent function module/special
function module.
Install a usable module.
The intelligent function module/
special function module is
experiencing a hardware fault.
(Contact your local Mitsubishi
representative.)
QCPU
Rem
2126
CPU module locations in a multiple
CPU system are either of the following.
There are empty slots between the
QCPU and QCPU/motion controller.
A module other than the High
Performance model QCPU/Process
CPU (including the motion controller)
is mounted on the left-hand side of
the High Performance model QCPU/
Process CPU.
Mount modules on the available slots
so that the empty slots will be located
on the right-hand side of the CPU
module.
Remove the module mounted on the
left-hand side of the High
Performance model QCPU/Process
CPU, and mount the High
Performance model QCPU/Process
CPU on the empty slot.
Mount the motion CPU on the right-
hand side of the High Performance
model QCPU/Process CPU.
Qn(H)
*3
QnPH
2128
The unusable module is mounted on
the extension base unit in the redundant
system.
Remove the unusable module from
the extension base unit.
QnPRH
*6
2150
In a multiple CPU system, the control
CPU of the intelligent function module
incompatible with the multiple CPU
system is set to other than CPU No.1.
Change the intelligent function
module for the one compatible with
the multiple CPU system (function
version B).
Change the setting of the control
CPU of the intelligent function module
incompatible with the multiple CPU
system to CPU No.1.
Q00J/Q00/
Q01
QnPH
QuU
2151
Either of the following modules
incompatible with the redundant system
has been mounted in a redundant
system.
CC-Link IE controller network
modules
MELSECNET/H
Ethernet interface modules
Use either of the following modules
compatible with the redundant system.
CC-Link IE controller network
modules
MELSECNET/H
Ethernet interface modules
QnPRH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*3 The function version is B or later.
*4 The function version is A.
*5 The module whose first 5 digits of serial No. is 04101 or later.
*6 The module whose first 5 digits of serial No. is 09012 or later.
*7 The Universal model QCPU except the Q02UCPU.
*8 This applies to the QnUDE(H)CPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.

Table of Contents

Related product manuals