• The file is the one which cannot be
specified by the sequence program
(such as comment file).
• The specified program exists in the
program memory, but has not been
registered in the program setting of
the Parameter dialog box.
This error may occur when the
ECALL, EFCALL, PSTOP, PSCAN or
POFF instruction is executed.
Read the individual information of the
error using the peripheral device, check
to be sure that the program
corresponds to the numerical values
there (program location), and correct.
QnA
Qn(H)
QnPH
QnPRH
QnU
2412
The SFC program file is one that cannot
be designated by the sequence
program.
Read the individual information of the
error using the peripheral device, check
to be sure that the program
corresponds to the numerical values
there (program location), and correct.
QnA
Qn(H)
QnPH
QnPRH
QnU
2413
No data has been written to the file
designated by the sequence program.
Read the individual information of the
error using the peripheral device, check
to be sure that the program
corresponds to the numerical values
there (program location), and correct.
Check to ensure that the designated file
has not been write protected.
QnA
Qn(H)
QnPH
QnPRH
2500
• There is a program file that uses a
device that is out of the range set in
the PLC parameter device setting.
• After the PLC parameter setting is
changed, only the parameter is
written into the programmable
controller.
• Read the common information of the
error using the peripheral device,
check to be sure that the parameter
device allocation setting and the
program file device allocation
correspond to the numerical values
there (file name), and correct if
necessary.
• If PLC parameter device setting is
changed, batch-write the parameter
and program file into the
programmable controller.
After the index modification of the PLC
parameter is changed, only the
parameter is written to the
programmable controller.
When the index modification of the PLC
parameter is changed, batch-write the
parameter and program file into the
programmable controller.
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*3 The function version is B or later.
*4 The function version is A.
*5 The module whose first 5 digits of serial No. is 04101 or later.
*6 The module whose first 5 digits of serial No. is 09012 or later.
*7 The Universal model QCPU except the Q02UCPU.
*8 This applies to the QnUDE(H)CPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.