TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 141
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3042
The system file that have stored the
remote password setting information is
damaged.
With GX Developer, write [PLC
parameter/Network parameter/
Remote password] to a valid drive
then reload the power supply for
system and/or reset the CPU module.
If the same error occurs, it is thought
to be a hardware error. (Contact your
local Mitsubishi representative.)
When a valid drive for parameter is
set to other than [program memory],
set the parameter file (PARAM) at the
boot file setting to be able to transmit
to the program memory.
With GX Developer, write [PLC
parameter/Network parameter/
Remote password] to a valid drive
then reload the power supply for
system and/or reset the CPU module.
If the same error occurs, it is thought
to be hardware error. (Contact your
local Mitsubishi representative.)
Qn(H)
*4
QnPH
*4
QnPRH
*4
3100
In a multiple CPU system, the CC-Link
IE controller network module controlled
by another CPU is specified as the
head I/O number of the CC-Link IE
controller network module.
Delete the network parameter of the
CC-Link IE controller network module
controlled by another CPU.
Change the setting to the head I/O
number of the CC-Link IE controller
network module controlled by host
CPU.
Qn(H)
*7
QnPH
*9
QnU
The network parameter of the CC-Link
IE controller network operating as the
normal station is overwritten to the
control station.
Or, the network parameter of the CC-
Link IE controller network operating as
the control station is overwritten to the
normal station.
(The network parameter is updated on
the module by resetting.)
Reset the CPU module.
Qn(H)
*7
QnPH
*9
QnPRH
*9
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q01CPU and is the answer not in the manual?

Mitsubishi Q01CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ01CPU
CategoryController
LanguageEnglish

Related product manuals