12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 145
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3100
In a multiple CPU system, the
MELSECNET/H under control of
another CPU is specified as the head I/
O number in the network setting
parameter of the MELSECNET/H.
Delete the MELSECNET/H network
parameter of the MELSECNET/H
under control of another CPU.
Change the setting to the head I/O
number of the MELSECNET/H under
control of the host CPU.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
The network parameter of the
MELSECNET/H operating as the
normal station is overwritten to the
control station.
Or, the network parameter of the
MELSECNET/H operating as the
control station is overwritten to the
normal station. (The network parameter
is updated on the module by resetting.)
Reset the CPU module.
Qn(H)
*1
QnPH
QnPRH
QnU
The number of actually installed
modules is different from that
designated in the number of modules
setting parameter of MELSECNET/H.
The head I/O number of actually
installed modules is different from
that designated in the network
parameter of MELSECNET/H.
Some data in the parameters cannot
be handled.
The network type of MELSECNET/H
is overwritten during power-on.
(When changing the network type,
switch RESET to RUN.)
The mode switch of MELSECNET/H
module
*5
is outside the range.
Check the network parameters and
actual mounting status, and if they
differ, make them matched.
If any network parameter has been
corrected, write it to the CPU module.
Check the extension base unit stage
No. setting.
Check the connection status of the
extension base units and extension
cables.
When the GOT is bus-connected to
the main base unit and extension
base units, also check the connection
status.
If the error occurs after the above
checks, the possible cause is a
hardware fault. (Contact your local
Mitsubishi representative, explaining a
detailed description of the problem.)
Set the mode switch of MELSECNET/
H module
*5
within the range.
QCPU
Although the QnACPU is a control
station or master station, the network
parameters have not been written.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.