12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 149
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3101
Since the number of points of the B/W
device set in [Device] of the PLC
parameter is lower than the number of
B/W refresh device points shown in the
following table when parameters of the
MELSECNET/H are not set, the refresh
between the CPU module and the
MELSECNET/H cannot be performed.
Set the refresh parameter of the
MELSECNET/H in accordance with the
number of points of B/W devices set in
[Device] of the PLC parameter.
Qn(H)
*6
QnPH
*6
QnPRH
*6
QnU
3102
A CC-Link IE controller network
parameter error was detected.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
Qn(H)
*6
QnU
The network module detected a
network parameter error.
A MELSECNET/H network parameter
error was detected.
The station No. specified in pairing
setting are not correct.
The stations are not numbered
consecutively.
Pairing setting has not been made for
the CPU module at the normal
station.
Refer to the troubleshooting of the
network module, and if the error is due
to incorrect pairing setting, reexamine
the pairing setting of the network
parameter.
QnPRH
The CC-Link IE controller network
module whose first 5 digits of serial No.
is "09041" or earlier is mounted.
Mount the CC-Link IE controller network
module whose first 5 digits of serial No.
is "09042" or later.
QnU
Paring setting in CC-Link IE controller
network modules installed in CPUs
except for Redundant CPUs was
performed.
Examine the paring setting for the
network parameter in the control staion.
Q00J/Q00/Q01
Qn(H)
*9
QnPH
*9
QnU
*9
LB/LW own station send range at LB/
LW4000 or later was set.
LB/LW setting (2) was performed.
Examine the network range
assignments for the network parameter
in the control station.
Q00J/Q00/Q01
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
No. of refresh device
points of B device
No. of refresh device
points of W device
1
8192 points
(8192 points 1
module
)
8192 points
(8192 points 1
module
)
2
8192 points
(4096 points 2
modules)
8192 points
(4096 points 2
modules
)
3
6144 points
(2048 points 3
modules
)
6144 points
(2048 points 3
modules
)
4
8192 points
(2048 points 4
modules)
8192 points
(2048 points 4
modules)
Refresh
device
No. of
mountable
network
modules
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.

Table of Contents