12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 151
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3103
In a multiple CPU system, the Q series
Ethernet interface module under control
of another station is specified to the
start I/O number of the Ethernet
network parameter.
Delete the Ethernet network
parameter of the Q series Ethernet
interface module under control of
another station.
Change the setting to the start I/O
number of the Q series Ethernet
interface module under control of the
host station.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
Although the number of modules has
been set to one or greater number in
the Ethernet module count
parameter setting, the number of
actually mounted module is zero.
The start I/O No. of the Ethernet
network parameter differs from the I/
O No. of the actually mounted
module.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
Rem
AJ71QE71 does not exist in the
position of I/O number set by the
parameter.
I/O number designation is
overlapping.
Numbers of the network parameter
and loaded AJ71QE71 are different.
Ethernet (parameter + dedicated
instruction) is set to more than five.
QnA
Ethernet module whose network type
is set to “Ethernet (main base)” is
mounted on the extension base unit
in the redundant system.
Ethernet module whose network type
is set to “Ethernet (extension base)”
is mounted on the main base unit in
the redundant system.
QnPRH
*6
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.