12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 151
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3103
In a multiple CPU system, the Q series
Ethernet interface module under control
of another station is specified to the
start I/O number of the Ethernet
network parameter.
• Delete the Ethernet network
parameter of the Q series Ethernet
interface module under control of
another station.
• Change the setting to the start I/O
number of the Q series Ethernet
interface module under control of the
host station.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
• Although the number of modules has
been set to one or greater number in
the Ethernet module count
parameter setting, the number of
actually mounted module is zero.
• The start I/O No. of the Ethernet
network parameter differs from the I/
O No. of the actually mounted
module.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
Rem
• AJ71QE71 does not exist in the
position of I/O number set by the
parameter.
• I/O number designation is
overlapping.
• Numbers of the network parameter
and loaded AJ71QE71 are different.
• Ethernet (parameter + dedicated
instruction) is set to more than five.
QnA
• Ethernet module whose network type
is set to “Ethernet (main base)” is
mounted on the extension base unit
in the redundant system.
• Ethernet module whose network type
is set to “Ethernet (extension base)”
is mounted on the main base unit in
the redundant system.
QnPRH
*6
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.