12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 157
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3300
The start I/O number in the intelligent
function module parameter set on
GX Configurator differs from the actual
I/O number.
Check the parameter setting.
QCPU
Rem
3301
The refresh setting of the intelligent
function module exceeded the file
register capacity.
The intelligent function module set in
GX Configurator differs from the
actually mounted module.
Change the file register file for the
one which allows refresh in the whole
range.
Check the parameter setting.
Q00J/Q00/Q01
Qn(H)
*1
QnPH
QnPRH
QnU
The intelligent function module's refresh
parameter setting is outside the
available range.
Check the parameter setting.
QCPU
Rem
3302
The intelligent function module's refresh
parameter are abnormal.
Check the parameter setting. QCPU
3303
In a multiple CPU system, the automatic
refresh setting or other parameter
setting was made to the intelligent
function module under control of
another station.
Delete the automatic refresh setting
or other parameter setting of the
intelligent function module under
control of another CPU.
Change the setting to the automatic
refresh setting or other parameter
setting of the intelligent function
module under control of the host
CPU.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
3400
The head I/O number of the target
module of the remote password is set to
other than 0
H to 0FF0H.
Change the head I/O number of the
target module to be within the 0
H to
0FF0
H range.
Qn(H)
*1
QnPH
QnPRH
QnU
*8
Rem
The head I/O number of the target
module of the remote password is set to
other than 0
H to 07E0H.
Change the head I/O number of the
target module to be within the 0
H to
07E0
H range.
Q02U
The head I/O number of the target
module of the remote password is
outside the following range.
Q00JCPU: 0
H to 1E0H
Q00CPU/Q01CPU: 0H to 3E0H
Change the head I/O number of the
target module of the remote password
for the number within the following
range.
Q00JCPU: 0
H to 1E0H
Q00CPU/Q01CPU: 0H to 3E0H
Q00J/Q00/
Q01
*1
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.

Table of Contents