TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 159
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3401
Position specified as the head I/O
number of the remote password file is
incorrect due to one of the following
reasons:
Module is not loaded.
Other than a the intelligent function
module (I/O module)
Intelligent function module other than
the Q series serial communication
module, modem interface module or
Ethernet module
Q series serial communication
module or Ethernet module of
function version A
The intelligent function module where
remote password is available is not
mounted.
Mount the Q series serial
communication module, modem
interface module or Ethernet module of
function version B or later in the position
specified in the head I/O No. of the
remote password file.
Qn(H)
*1
QnPH
QnPRH
QnU
Rem
Any of the following modules is not
mounted on the slot specified for the
head I/O number of the remote
password.
Serial communication module of
function version B or later
Ethernet module of function version B
or later
Modem interface module of function
version B or later
Mount any of the following modules in
the position specified for the head I/O
number of the remote password.
Serial communication module of
function version B or later
Ethernet module of function version B
or later
Modem interface module of function
version B or later
Q00J/Q00/
Q01
*1
The Q series serial communication
module, modem interface module or
Ethernet module of function version B
or later controlled by another CPU was
specified in a multiple CPU system.
Change it for the Ethernet module of
function version B or later connected
by the host CPU.
Delete the remote password setting.
Qn(H)
*1
QnPH
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*4 The module whose first 5 digits of serial No. is 04012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*7 The module whose first 5 digits of serial No. is 09012 or later.
*8 The Universal model QCPU except the Q02UCPU.
*9 The module whose first 5 digits of serial No. is 10042 or later.