12
TROUBLESHOOTING
12.3 Error Code List
12.3.6 Error code list (4000 to 4999)
12 - 165
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
*3 The module whose first 5 digits of serial No. is 04012 or later.
*4 The module whose first 5 digits of serial No. is 07012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The module whose first 5 digits of serial No. is 09012 or later.
*7 The Universal model QCPU except the Q02UCPU.
*8 This applies to the QnUDE(H)CPU.
4101
• The number of setting data dealt with
the instruction exceeds the applicable
range.
• The storage data and constant of the
device specified by the instruction
exceeds the applicable range.
• When writing to the host CPU shared
memory, the write prohibited area is
specified for the write destination
address.
• The range of storage data of the
device specified by the instruction is
duplicated.
• The device specified by the
instruction exceeds the range of the
number of device points.
• The interrupt pointer No. specified by
the instruction exceeds the applicable
range.
• The block data that crosses over the
boundary between the internal user
device and the extended data register
(D) or extended link register is
specified (including 32-bit binary, real
number (single precision, double
precision), indirect address, and
control data)
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
Rem
• The storage data of file register
specified by the instruction exceeds
the applicable range. Or, file register
is not set.
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU