12
TROUBLESHOOTING
12.3 Error Code List
12.3.6 Error code list (4000 to 4999)
12 - 175
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
*3 The module whose first 5 digits of serial No. is 04012 or later.
*4 The module whose first 5 digits of serial No. is 07012 or later.
*5 The module whose first 5 digits of serial No. is 07032 or later.
*6 The module whose first 5 digits of serial No. is 09012 or later.
*7 The Universal model QCPU except the Q02UCPU.
*8 This applies to the QnUDE(H)CPU.
4230
The number of CHK and CHKEND
instructions is not equal.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
QnA
Qn(H)
QnPH
4231
The number of IX and IXEND
instructions is not equal.
4235
The configuration of the check
conditions for the CHK instruction is
incorrect.
Alternatively, a CHK instruction has
been used in a low speed execution
type program.
QnA
Qn(H)
QnPH
4300
The designation of a MELSECNET/
MINI-S3 master module control
instruction was wrong.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
QnA
4301
The designation of an AD57/AD58
control instruction was wrong.
4350
The target CPU module specified by
the multiple CPU high-speed
transmission dedicated instruction,
specified by the program is wrong.
Or, the multiple CPU high-speed
transmission dedicated instruction
cannot be set in the setting.
The reserved CPU is specified.
The uninstalled CPU is specified.
The head I/O number of the target
CPU/16 (n1) is outside the range of
3EH to 3E3H.
The CPU module where the
instruction cannot be executed is
specified.
The instruction is executed in a single
CPU system.
The host CPU is specified.
The multiple CPU high-speed
transmission dedicated instruction
was executed when "Use multiple
CPU high speed transmission" is not
selected.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q01CPU and is the answer not in the manual?

Mitsubishi Q01CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ01CPU
CategoryController
LanguageEnglish

Related product manuals