TROUBLESHOOTING
12.3 Error Code List
12.3.7 Error code list (5000 to 5999)
12 - 185
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
5000
The scan time of the initial execution
type program exceeded the initial
execution monitoring time specified in
the PLC RAS setting of the PLC
parameter.
Read the individual information of the
error from the peripheral device,
check its value (time), and shorten
the scan time.
Change the initial execution
monitoring time or the WDT value in
the PLC RAS setting of the PLC
parameter.
Resolve the endless loop caused by
jump transition.
QnA
Qn(H)
QnPH
QnPRH
QnU
The power supply of the standby
system is turned OFF.
The tracking cable is disconnected or
connected without turning off or
resetting the standby system.
The tracking cable is not secured by
the connector fixing screws.
Since power-off of the standby
system increases the control system
scan time, reset the WDT value,
taking the increase of the control
system scan time into consideration.
When the tracking cable is
disconnected during operation,
securely connect it and restart the
CPU module. If the same error is
displayed again, the tracking cable or
CPU module has a hardware fault.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
QnPRH

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q01CPU and is the answer not in the manual?

Mitsubishi Q01CPU Specifications

General IconGeneral
BrandMitsubishi
ModelQ01CPU
CategoryController
LanguageEnglish

Related product manuals