12
TROUBLESHOOTING
12.3 Error Code List
12.3.7 Error code list (5000 to 5999)
12 - 189
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
5010
The program scan time exceeded the
constant scan setting time specified in
the PLC RAS setting of the PLC
parameter.
• Review the constant scan setting
time.
• Review the constant scan setting time
and low speed program execution
time in the PLC parameter so that the
excess time of constant scan can be
fully secured.
QnA
Qn(H)
QnPH
QnPRH
QnU
The low speed program execution time
specified in the PLC RAS setting of the
PLC parameter exceeded the excess
time of the constant scan.
QnA
Qn(H)
QnPH
QnPRH
The program scan time exceeded the
constant scan setting time specified in
the PLC RAS setting of the PLC
parameter.
Review the constant scan setting time
in the PLC parameter so that the excess
time of constant scan can be fully
secured.
Q00J/Q00/Q01
5011
The scan time of the low speed
execution type program exceeded the
low speed execution watch time
specified in the PLC RAS setting of the
PLC parameter dialog box.
Read the individual information of the
error using the peripheral device, check
the numerical value (time) there, and
shorten scan time if necessary. Change
the low speed execution watch time in
the PLC RAS setting of the PLC
parameter dialog box.
QnA
Qn(H)
QnPH
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU