TROUBLESHOOTING
12.3 Error Code List
12.3.8 Error code list (6000 to 6999)
12 - 213
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
6400
The memory copy from control system
to standby system was executed, and
the program memory was cleared.
After the memory copy from control
system to standby system is completed,
switch power OFF and then ON, or
make a reset.
QnPRH
6410
The memory copy from control system
to standby system was executed.
(This can be detected from the control
system of the redundant system.)
–
6500
The file register file specified in the
tracking setting of the PLC parameter
dialog box does not exist.
Read the individual information of the
error using GX Developer, and check
and correct the drive name and file
name. Create the specified file.
QnPRH
6501
The file register range specified in the
device detail setting of the tracking
setting of the PLC parameter dialog box
exceeded the specified file register file
capacity.
Read the individual information of the
error using GX Developer, and increase
the file register capacity.
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU