12
TROUBLESHOOTING
12.3 Error Code List
12.3.9 Error code list (7000 to 10000)
12 - 217
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
*3 The Universal model QCPU except the Q02UCPU.
*4 The module whose first 5 digits of serial No. is 09082 or later.
*5 Abbreviation for "MELSEC-Q series-compatible PC CPU module bus interface driver software package"
7004
In a multiple CPU system, a data error
occurred in communication between the
CPU modules.
Check the system configuration to
see if modules are mounted in excess
of the number of I/O points.
When there are no problems in the
system configuration, this indicates
the CPU module hardware is faulty.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
Q00/Q01
*1
QnU
7010
In a multiple CPU system, a faulty
CPU module was mounted.
In a multiple CPU system, a CPU
module incompatible with the multiple
CPU system was mounted. (The CPU
module compatible with the multiple
CPU system was used to detect an
error.)
In a multiple CPU system, any of the
CPU No. 2 to 4 was reset with power
ON. (The CPU whose reset state was
cancelled was used to detect an
error.)
Read the individual information of the
error using GX Developer, and
replace the faulty CPU module.
Replace the CPU module with the
one compatible with the multiple CPU
system.
Do not reset any of the No. 2 to 4
CPU modules.
Reset CPU No. 1 and restart the
multiple CPU system.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
The PC CPU module-compatible
software package (PPC-DRV-01)
*5
whose version is 1.06 or earlier is used
in a multiple CPU system.
Change the version of the PC CPU
module-compatible software package
(PPC-DRV-01)
*5
to 1.07 or later.
Q00/Q01
*1
The Q172(H)CPU(N) or
Q173(H)CPU(N) is mounted on the
multiple CPU high-speed main base
unit (Q3 DB). (This may result in a
module failure.)
Replace the Q172(H)CPU(N) and
Q173(H)CPU(N) with the Motion CPU
compatible with the multiple CPU high-
speed main base unit.
Qn(H)
*4
QnPH
*4
The Universal model QCPU (except
Q02UCPU) and Q172(H)CPU(N) are
mounted on the same base unit. (This
may result in a module failure.)
Check the QCPU and Motion CPU that
can be used in a multiple CPU system,
and change the system configuration.
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding