MELSEC-Q
10 DEVICES
Timer Processing and accuracy
(a) When an OUT T instruction is executed, the following is processed: timer
coil ON/OFF, current value update and contact ON/OFF processing. Timer
current value update and contact ON/OFF processing are not performed at
END processing.
Processing content
Coil ON/OFF
Current value updat
Contact ON/OFF
X0
T0
K10
[Ladder example]
Sequence
program
END OUT T0 END
[Processing at execution of OUT T0 instruction]
(b) When the OUT T instruction is executed, the current value is added to the
scan time measured at the END instruction.
If the timer coil is OFF when the OUT T
instruction is executed, the
current value is not updated.
X0
T0
H
[Ladder example]
K8
QCPU's X0
211 121 121
23 23 23
2+3=5
0+2=2 5+2=7 7+3=10
OUT T0
END
processing
OUT T0 OUT T0
OUT T0
OUT T0
OUT T0
Input reading timing
(+1 scan)
Timer accuracy
- (1 scan time + timer time
limit settin