MODINE CONTROLS SYSTEM MANUAL
ClassMate and SchoolMate Models
AIR74-525.1
Data Logger Sub Menu
To access contents of the Data Logger menu simply
press the ENTER button. The most recent alarm will be
displayed on the screen. The upper bar will display the
time and date of the most recent alarm. The second
line will indicate the alarm generated. The rest of the
page will contain readings of certain variables at the
time of the alarm.
Use the UP button to navigate through previous alarms
and the DOWN button to navigate to the most recent.
The alarms are chronologically stored and the most
recent alarm will be the first displayed.
Main Status Screen = Data Logger
Figure 18.1 Alarm Log
Board Switch Sub Menu
The Board Switch screen will indicate the current
devices connected to the pLAN network (Keypad and
pAD Wall Stat). In the screen below, the main controller
is on address 1.
The pCOOEM+ controller is factory defaulted to the
following for modules communiated with on the pLAN:
Main Status Screen = Board Switch
Figure 18.2 Board Switch
● pCOOEM+ Controller: Address1
● Remote Wall Stat (pAD): Address 4
● Remote Display (pGD1): Address 32
In the situation that module addresses need to be set
up, the board address can be changed within the Board
Switch sub menu