Engineering
18
12/03 AWB-C27-1293GB
DeviceNet
Precondition: For communication through
DeviceNet, the firmware version of the MI4 units
must be 4.40 or later. In addition, the ZB4-506-IF1
interface module must be connected (see
Section “Interface module”, page 30).
The connection to a PLC with the DeviceNet protocol
is made through the AUX PORT of the MI4. The AUX
PORT supports RS 485 communications.
Figure 7: DeviceNet communication cable
ZB4-209-DS1 plug
Bus terminating resistor
1
SUB D
AUX PORT
9
2CAN_L
3GND
5 CAN_SHLD
7CAN_H
9 +24 V (Input)
a
b
5
9
3
Bare
V+(red)
V-(black)
CAN_H(white)
CAN_L(blue)
DeviceNet
7
2
3
5
1
2
3
4
5
1
4
2
121 O G1 %
0.25 W
MI4
AUX PORT