ioLogik E1200 Series Using the Web Console
Standard Trap
The ioLogik E1200 series remote I/O provides the following standard SNMP traps:
Trigger Type Description
coldStart Sends SNMP trap when the agent reinitializes.
*Restart the measurement epochs because configuration data or MIB variables
may have changed.
warmStart Sends SNMP trap when the /etc/snmpd.conf file is reread and the agent
reinitializes.
*Do NOT restart the measurement epochs because configuration data or MIB
variable values have not changed. The configuration information in the
/etc/snmpd.conf file is for agent configurations that do not affect
databases.
Private Trap
The ioLogik E1200 series remote I/O provides the following private trap triggers:
Trigger Type Description
DI-change status Sends SNMP trap when DI status changes.
DO-change status Sends SNMP trap when DI status changes.
Relay-change status Sends SNMP trap when Relay status changes.
AI-burn-out Sends SNMP trap when AI reaches preset burn-out value.
AI-trigger Sends SNMP trap when AI reaches preset value.
AO-trigger Sends SNMP trap when AO reaches preset value.
RTD-trigger Sends SNMP trap when RTD reaches preset value.
TC-trigger Sends SNMP trap when TC reaches preset value.
Using SNMP
Moxa has provided the ioLogik E1200 MIB file for easier analysis of SNMP data.
SNMP Agent
You can enable SNMP under SNMP Settings SNMP Agent. SNMP is used to monitor the network and I/O
devices with SNMP network management software. Use these fields to enable SNMP and set the read and write
community names, contact, and location for SNMPv1 and SNMPv2c.
need to load the correct MIB file to use Moxa’s private SNMP traps.