6 Installation and commissioning
54 5831400/02 EN
3. Route a sufficient length of connection cable through the cable gland and
adapter and tighten the cable gland.
Figure34: Cable gland
Also refer to
2 Connecting cable glands/NPT adapters [►74]
6.4.4.4 EMC double cable gland (accessory)
Use shielded conductors for the Modbus wiring and connect the shield on
both sides (same shielding potential for all devices).
We recommend EMC cable glands, which are commercially available as
EMC single cable glands.
Depending on the device version and choice of connection cables, using an
EMC double cable gland may be useful. You can order these as acces-
sories from Maschinenfabrik Reinhausen GmbH:
▪ EMC double cable gland: material no. 10173481
You will find the technical drawing for this EMC double cable gland in the ap-
pendix.
The EMC double cable gland is suitable for cables with an ex-
ternal diameter of 8.7mm
+
/
-
10%.