B-10
Possible trouble conditions:
Chillgard RT Remote Relay Module losing communication with the
Chillgard RT Refrigerant Monitor for longer than two seconds
Refrigerant Monitor internal trouble
Relay Module inoperative relay.
See Section 4, Troubleshooting Guidelines for other possible trouble
conditions.
Ready Indicator
The Ready Indicator turns ON and stays ON when the controlling
Chillgard RT Refrigerant Monitor is ready and Relay Module is
operating properly
This indicator remains OFF during the initial warm-up
This indicator remains OFF during the initial Chillgard RT
Refrigerant Monitor warm-up, setup and calibration.
Chillgard RT Relay Module Relays
There are three types of relays in the Chillgard RT Relay Module:
common horn relay
common trouble relay
discrete alarm relays
The Common Horn Relay:
is a double-pole, double-throw (DPDT) type relay
contacts are normally connected to equipment to alert personnel of
an alarm condition
The Trouble Relay:
is a double-pole, double-throw (DPDT) type relay
is normally-energized during normal operation for fail-safe
operation
de-energizes if power is removed
contacts may be connected to equipment to alert personnel that a
trouble condition exists