B-13
Horn Operation
C
onfiguration
The configuration of the horn relay is controlled by the Chillgard RT
Refrigerant Monitor.
• Th
e Horn Relay in the Relay Module is configured by the “Caution
sets A
udio Alarm,” “Warning sets Audio Alarm,” “Alarm sets Audi
o
A
larm” and "Trouble sets Audio Alarm" configuration in t
he
C
hillgard RT Refrigerant Monitor.
• Th
e "Aux sets Audio Alarm" and "Trouble sets Audio Alarm"
configurations of the Refrigerant Monitor apply to the Relay Modul
e
H
orn relay.
• Th
e Horn relay of the Relay Module is only latching when the
a
larms are configured latching in the Chillgard RT Refrigerant
Monitor.
Reset Switch
The reset switches of the Chillgard RT Relay Module and controlling
Chillgard RT Refrigerant Monitor act independently. Pressing the reset
switch on the Refrigerant Monitor does not affect the Relay Module
horn, and pressing the reset switch on the Relay Module does not affect
the Refrigerant Monitor horn. If the Chillgard RT Relay Module reset
switch has been used to silence the Relay Module horn, and any alarm
condition (configured to activate the horn) occurs at a new sequencer
point, t
he horn relay will activate to signal the new alarm condition.
Maintenance
Under normal operating conditions, the Chillgard RT Relay Module
requires no maintenance. However, periodic testing of the relays may
be done to ensure that complete system operation is possible.