1-12
Ta
ble 1-7. Typical Chillgard RT System for
R-113 Cross-Sensitivity Response Data
GAS CONCENTRATION (PPM) EQUIVALENT PPM R-113
R11 100 1
R12 100 10
R22 100 5
R123 100 125
R134A 100 175
R114 100 155
R113 100 100
TEST CONDITIONS: Calibrated 0-1000 PPM R-113 in N
2
; Temperature: 25°C
Table 1-8. Typical Chillgard RT System for
R-113 Cross-Sensitivity Response Data
GAS CONCENTRATION (PPM) EQUIVALENT PPM R-114
R11 100 105
R12 100 50
R22 100 35
R113 100 30
R123 100 3
R134a 100 20
R114 100 100
TEST CONDITIONS: Calibrated 0-1000 PPM R-114 in N
2
; Temperature: 25°C
Table 1-9. Typical Chillgard RT System for
R-500 Cross-Sensitivity Response Data
GAS CONCENTRATION (PPM) EQUIVALENT PPM R-500
R11 100 8
R22 100 0
R113 100 41
R114 100 60
R123 100 2
R134a 100 7
R502 100 5
R500 100 100
TEST CONDITIONS: Calibrated 0-1000 PPM R-500 in N
2
; Temperature: 25°C