MSA
Approvals
PrimaX
54
GB
PrimaX I
Special conditions for safe use:
- It is not allowed to open the key pad cover by operations at Category II Ga and
Group IIC.
- The device shall only be used in areas known to have a low risk of mechanical
impact if installed in Group II Db.
Manufacturer: MSA AUER GmbH
Thiemannstraße 1
D-12059 Berlin
Product: PrimaX I
Type of protection: IEC 60079-0:2007, IEC 60079-11:2006,
IEC 60079-26:2006, IEC 61241-11:2005
Measuring function for explosion protection: no
Gas: see manual
Marking: Prima X I
Ex ia IIC T4 Ga
Ex ia IIIC T130°C Db
-40°C Ta +70°C
P
i
770 mW, U
i
28 V, I
i
110 mA, L
i
= 0, C
i
= 0
Option: HART Module Connector, only for temporary connection of
an intrinsic safe HART Field Communicator
P
o
770 mW, U
o
28 V, I
0
110 mA, L
o
10 µH, C
o
1nF
P
i
5mW, U
i
5 V, I
i
1 mA, L
i
= 0, C
i
= 0
IEC-Type Examination Certificate:IECEx BVS 10. 0043 X
Quality Assurance Notification: 0158
Year of Manufacture: see Label
Serial Nr.: see Label