Section 40 00-02-0716
2013-06-03 - 9 -
Use the following steps to select the correct start/stop:
1. Access the S numbers menu by pressing [Menu].
2. Use the [Up Arrow] and [Down Arrow] to scroll to the correct Entry Code (See Entry Code
Supplement for Entry Codes).
3. When the correct Entry Code is displayed, press [Enter] to access the S numbers menu.
NOTE: If the incorrect code is entered, “PASSWORD FAILURE” will appear on
the display. Press [Enter] and try again.
NOTE: S35 is the S-Number used for the start/stop type. See the S number
section of this manual for details.
4. Press the [Up Arrow] and [Down Arrow] until (S35) START/STOP SELECT is displayed,
press [Enter] to highlight the current setting.
5. Press the [Up Arrow] and [Down Arrow] until the desired selection is displayed, press
[Enter] to un-highlight the new setting.
6. Exit the S Menu by pressing [Menu].
System Throttling Types
There are (3) throttling types in S37: MAX. RPM, TRANSDUCER, LOCAL THROTTLE.
Max. RPM:
The Engine is throttled to the max. rpm set point.
Transducer:
A transducer is used for auto throttling. There are set points, allowing the operator to enter the
appropriate values.
Local Throttle:
An external 0-5 vdc potentiometer is used for auto throttling. There are set points, allowing the operator
to enter the appropriate values.
Use the following steps to select the correct transducer type:
1. Access the S numbers menu by pressing [Menu].
2. Use the [Up Arrow] and [Down Arrow] to scroll to the correct Entry Code (See Entry Code
Supplement for Entry Codes).
3. When the correct Entry Code is displayed, press [Enter] to access the S numbers menu.
NOTE: If the incorrect code is entered, “PASSWORD FAILURE” will appear on
the display. Press [Enter] and try again.