Configuration/settings
User manual 55530_hdb_en_16 126 / 156
8.12 Factory settings
Reset to factory set-
tings - retain I&M data
The Reset to factory settings - I&M data retained function resets the mod-
ule to its factory settings but retains the I&M data saved in memory.
Proceed as follows:
Click Connect online in the TIA portal.
After connection, mark the module in question.
Open the MVK-MPNIO module in project navigation.
Double-click Online & Diagnostics.
Below the Functions tab, click Reset to factory settings to open a win-
dow.
Activate the Retain I&M data selection.
Press the Reset button.
The module is reset to the factory setting.
Reset to the factory
settings - default val-
ues
Tab. 8-44: Reset to factory settings - default values
Reset to the factory
settings - I&M values
Tab. 8-45: Reset to factory settings - I&M values
Setting Value
IP address 0.0.0.0
Subnet mask 0.0.0.0
Router address 0.0.0.0
PROFINET device name Empty
I&M values Value
System ID code Empty
Place identifier Empty
Installed date Empty
Description Empty
Additional information Empty