Configuration/settings
User manual 55530_hdb_en_16 128 / 156
Reset to factory set-
tings - delete I&M data
The Reset to factory settings - Delete I&M data function resets the module
to the factory settings and, at the same time, deletes the I&M data stored in
memory.
Proceed as follows:
Click Connect online in the TIA portal.
After connection, mark the module in question.
Open the MVK-MPNIO module in project navigation. Double-click Online
& Diagnostics.
Below the Functions tab, click Reset to factory settings to open a win-
dow.
Activate the Delete I&M data menu option.
Press the Reset button.
The module is reset to the factory setting.