Events Meaning
Battery low Battery low
Communic lost Communication between the UPS and the device has been interrupted
SENTR level 2
Presence of an internal UPS failure (this condition emulates the level
of modem alarm for UPSs of the SENTR type)
SENTR level 3
Presence of a failure in the UPS, excluding those envisaged in the
previous point (this condition emulates the level of modem alarm for
UPSs of the SENTR type)
Email config menu
/------------------------/
/ Email config /
/------------------------/
Email address 1:myself@mycompany.com
Email address 2:service@service.com
Email address 3:anotheremail@mycompany.com
Sender address.:NetMan_plus
Customer.......:MyCustomer
Report interval:01.05:10 DD-HH:MM
User name......:User 1
Password.......:Password
This menu may be used to configure the addresses to which to send the alarm notification and
report e-mails and other parameters of the e-mail service as described in the following table.
Field Parameters to be inserted
Email address 1
Enter the e-mail addresses to which to send the alarm notifications and
reports (see note).
Email address 2
Email address 3
Sender address Enter the address from which the e-mails are sent.
(1)
Customer
Enter an identifying string; this additional information is included in the e-
mail.
Report interval
Enter the delay, measured in days, between the sending of one report e-
mail and the next by using exactly 2 figures, followed by a dot, an finally by
the hour and minutes on which the email should be sent.
User name If the server requires authentication, insert the “User name”.
Password If the server requires authentication, insert the password.
(1)
do not use the “space” character in this field
After inserting the data and pressing the “ESC” key to exit from the menu, the service can be
tested by pressing the “T” key. If the test is performed, a “@” is displayed and a test email is sent
to all the configured email addresses. After this the previous menu is shown.
report e-mails are sent to all the addresses inserted; for alarm notification e-mails see
paragraph “Email logic menu”