COOLING SETTINGS (HEAT PUMP WITH COOLING
FUNCTION REQUIRED)
cooling1.9.5
delta at +40 °C
delta at +20 °C °C
°C
°C
DM
cool/heat sensor
heat at room under temp.
set pt value cool/heat sensor
BT74
cooling1.9.5
set pt value cool/heat sensor
heat at room under temp.
cool at room over temp.
use room sensor
°C
°C
°C
delta at +20 °C
Setting range: 3 10 °C
Factory setting: 3
delta at +40 °C
Setting range: 3 20 °C
Factory setting: 6
Menu
1.9.5
cool/heat sensor
Setting range: BT74 (BT50, RMU-BT50)
Factory setting: BT74
set pt value cool/heat sensor
Setting range: 5 40 °C
Factory setting: 21
heat at room under temp.
Setting range: 0.5 10.0 °C
Default value: 1.0
cool at room over temp.
Setting range: 0.5 10.0 °C
Default value: 3.0
NIBE SMO 40Chapter 3 | SMO 40 at your service40