AUTO MODE SETTING
start cooling
stop heating
stop additional heat
filtering time
°C
°C
°C
hrs
auto mode setting4.9.2
start cooling
Setting range: -20 40 °C
Factory setting: 25
stop heating
Setting range: -20 40 °C
Default values: 17
stop additional heat
Setting range: -25 40 °C
Factory setting: 5
filtering time
Setting range: 0 48 h
Default value: 24 h
Menu
4.9.2
When the operating mode is set to "auto", the control module selects when start
and stop of additional heat and heat production is permitted, depending on the
average outdoor temperature. If the heat pump has the integrated cooling function
and it is activated in the menu you can also select the start temperature for
cooling.
Select the average outdoor temperatures in this menu.
Caution
It cannot be set "stop additional heat" higher than "stop heating".
filtering time: You can also set the time (filtering time) over which the average
temperature is calculated. If you select 0, the current outdoor temperature is
used.