108 Chapter 6 Parameter description
Fig.6-2 Schematic diagram for acceleration/deceleration time
Note:
The default value of acceleration and deceleration time:
7.5kW and below: 6.0 seconds
11kW~22kW: 20.0 seconds
30kW~110kW: 60.0 seconds
132kW and above: 90.0 seconds
6.2 Start and stop group (F1)
②
F1.00 Start mode
Range: 0~1【0】
③
F1.00 Start mode
Range: 0~2【0】
0: Start directly
The inverter starts according to the start frequency (F1.01) and the start
frequency holding time (F1.02).
1: DC brake first and then start at start frequency
The inverter performs DC braking first and then starts in mode-0. It is
applicable to the applications of small inertia loads where reverse rotation is