NE200/300 Series Drive User Manual
Chapter 6 Parameter description 99
Chapter 6 Parameter description
Note:
The value in the 【】indicates the factory default value of the parameter.
6.1 Group 0 Basic Function
F0.00 Reserved
Range:
Drive type display
0~10
This parameter of NE200 is reserved, show the type of drive of NE300.
0: Type G (Heavy duty)
1: Type P (Normal duty)
F0.01 Control mode Range: 02 0
0: No vector Sensor vector control-1
This mode offers excellent vector control performance while insensitive
to motor parameters. It is applicable to most applications.
1: No vector Sensor vector control-2
Precise speed sensor-less vector control technology realizes AC motor
decoupling, enabling the DC motorization of running control. Its applicable
to high performance applications and features high precision of speed and
torque and eliminates the need for pulse encoder.
2:
Reserved
2:
Vector control with encoder
3: V/F control
It is applicable to the common applications where load requirement is
not high such as fan and pump loads. It can be also used in
applications where one drive drives multiple motors.