NE200/300 Series Drive User Manual
Chapter 6 Parameter description 135
setting value of 100~300 will take suppression effect.
6.6 Motor parameters group (F5)
F5.00 Motor type Range: 0~2【0】
F5.01 Motor polarity
number
Range: 2~56【4】
F5.02 Rated power
【Depends on model】Range:
②
0.1~6553.5kW
0.4~999.9kW
F5.03 Rated current
【Depends on model】Range:
②
0.01~655.35A
0.1~999.9A
F5.04 Rated rotation
speed
【Depends on model】Range:
②
0~65535RPM
0~24000
F5.00~F5.04 are used to set the controlled motor parameters. In order
to ensure the control performance, please set F5.00~F5.04 correctly by
referring to values on motor nameplate.
Note:
On V/F control, the motor power shall be matched to the drive power.
Normally the motor power is only allowed to be 2 steps lower than that of the
drive or 1 step higher. While in SVC or VC control, the motor power must
exactly match that of the drive, otherwise, the control performance could not
be ensured.