NE200/300 Series Drive User Manual
Chapter 3 Wiring of Drive 27
Output AC
reactor
When the cable connecting the drive and the motor is longer than 100m, it is
suggested to install AC output reactor to suppress the high-frequency
oscillation to avoid the damage to motor insulation, large leakage current and
frequent drive protective actions.
3.3 Main Circuit Peripheral Devices Guide
Table 3-1 NE200-4T0040G/0055PB and below
Drive Mode
Circuit Breaker
A
Contactor
A
R
、
S
、
T
、
P1
、
(+)
、
PB
、
(-)
、
U
、
V
、
W
Grounding terminal PE
Terminal screw
Tightening
torque (N·m)
Wire spec.
(mm
2
)
Terminal screw
Tightening
torque (N·m)
Wire spec.
(mm
2
)
NE200-2S0004GB
NE200-2S0007GB
NE200-2S0015GB
NE200-4T0007G/0015PB
NE200-4T0015G/0022PB
NE200-4T0022GB -M
NE200-2S0022GB
NE200-4T0022G/0040PB
NE200-4T0040G/0055PB
Table 3-2 NE300-4T0220G/0300PB and below
Drive Mode
Circuit Breaker
A
Contactor
A
R
、
S
、
T
、
P1
、
(+)
、
PB
、
(-)
、
U
、
V
、
W
Grounding terminal PE
Terminal screw
Tightening torque
(N·m)
Wire spec.
(mm
2
)
Terminal screw
Tightening torque
(N·m)
Wire spec.
(mm
2
)
NE300-4T0022G/0040PB 16 10 M4
1.2
~
1.5
2.5
M4
1.2
~
1.5
2.5