NE200/300 Series Drive User Manual
100 Chapter 6 Parameter description
F0.02 Run command control mode Range: 0~2 【0】
0: Operation keypad control (“LOCAL/REMOT” indicator OFF)
Running commands are controlled by RUN and STOP keys on
operation keypad.
1: Terminal control (“LOCAL/REMOT” indicator ON)
Running commands are controlled by the multifunctional input
terminals such as FWD, REV, JOGF, JOGR, etc.
2: Serial communication control (“LOCAL/REMOT” indicator blinks)
Start & stop is controlled by the communication serial port. Modbus
card is inbuilt.
F0.03 Frequency reference 1
(Freq. ref. 1)
Range: 0~8 【0】
F0.04 Frequency reference 2
(Freq. ref. 2)
Range: 1~8 【1】
0: Digital setup
The initial value is the value of F0.06 “UP/DOWN preset frequency”.
The reference frequency value can be changed through the keys “▲”
and “▼” on the keypad or multi-function terminals UP/DOWN (select
through F0.08). The modification recording options in case of power
failure is determined by the parameter F0.09. If setting is not saved in
power failure, the reference frequency value will recover to default
value F0.06 “UP/DOWN Preset Frequency” upon power recovery.
1: Terminal AI1
2: Terminal AI2
It means that the frequency is determined by the analog input terminal.
AI1 refers to voltage input 0~10V. AI2 can be used as either voltage
input of 0V~10V or current input of 0/4mA ~20mA, which can be