NE200/300 Series Drive User Manual
120 Chapter 6 Parameter description
frequency
0: Enabled
1: Disable
F2.26 ENTER key function Range:0~3【0】
0: No special action
1: Fwd/Rev switching: When the keypad control the start and stop, press
ENTER key under monitoring status will switch the rotation direction.
2: Under monitoring status, Run for forward; Enter for Reverse; STOP for
stop.
3: Jog running
Note:
When MFK key defines RUN as forward, MFK as reverse, and STOP as
stop (FE.01=7), the ENTER key shall not switch the rotation direction.
F2.27 Freq. resolution Range:0~1【0】
0: 0.01Hz. The drive Max running frequency can be up to 320.0Hz.
1: 0.1Hz. The drive Max running frequency can be up to 3200.0Hz.
F2.28 Acc./Dec time unit Range:0~1【0】
0: 0.1s. The drive longest Acc./Dec time is 3600 seconds
1: 0.01s. The drive longest Acc./Dec time is 360 seconds
F2.29 High freq. modulation mode
Range:0~1【0】
0: Asynchronous modulation
1: Synchronous modulation
When the frequency resolution is 0.01Hz, the regulation is fixed to be
asynchronous modulation. When the frequency resolution is 0.1Hz, the
regulation is asynchronous if this parameter F2.29=0; if this parameter