NE200/300 Series Drive User Manual
152 Chapter 6 Parameter description
Value
Function Description
10
Reserved Reserved
10
Indicate the
running step
(Co-setting in
DO\Y1\Y2)
It indicates the present running step. Refer to
table 6-7 for details.
11
Ready for running
(RDY)
When the main circuit and control circuit is
power up and there is no fault protection action,
the drive is ready for running and then terminal
output ON signal.
12 Timing arrival
When multi-function input terminal defined as
No.38 is active, the drive starts timing. And when
the running time exceeds the F7.14 preset time,
it output ON signal. The timing is cleared to zero
if the input terminal is invalid.
13 Counting arrival
When the counting value reach the value
defined in F7.13, it output ON signal.
14 Reserved Reserved
15
Preset torque value
arrival
When motor's torque exceeds reference value
(set by P7.12), terminal outputs ON signal.
16 Drive fault output When the drive is faulty, it outputs ON signal.
17
Under voltage status
output
When the drive is in under voltage status,
terminal outputs ON signal.
18
Drive overload
pre-warning
If the output current is higher than the value
defined by FC.02 (Overload Pre-alarm detection
level), terminal outputs ON signal.
19
Fixed-length arrived,
output a high level
signals
If the actual length exceeds the preset length,
terminal outputs ON signal.
20 PID in dormancy
When PID is in dormancy, terminal outputs ON
signal.
21 AI1>AI2
When AI1>AI2 value, terminal outputs ON
signal.
22 AI1<F7.16 When AI1<F7.16, terminal outputs ON signal.
23 AI1>F7.16 When AI1>F7.16, terminal outputs ON signal.
24 F7.16<AI1<F7.17 When F7.16<AI1<F7.17, terminal outputs ON