NE200/300 Series Drive User Manual
Chapter 6 Parameter description 167
2: Continuous operation
The drive will start next cycle of operation automatically after
completing one cycle of PLC operation until receiving STOP
command.
F9.08 PLC restarting mode after
interrupt
Range: 0~1【0】
0: Restart from first step
If the drive stops during PLC operation because of receiving STOP
command or fault, or power loss, it will restart from the first step after
restarting.
1: Continue from the step where the drive was interrupted
When the drive stops during PLC operation because of receiving
STOP command or fault, it will record the already running time of the
present step. After restart, the drive automatically enters the specific
step where it was interrupted and run the left time of this step with the
step frequency.
F9.09 PLC status recorded or not at
power failure
Range: 0~1【0】
If F9.09 is set to 1, the PLC operating parameters such as the PLC
operating step and PLC operating time will be saved when power loss.
0: Not save 1: save
F9.10 Time unit select for each duration
of PLC processing
Range: 0~1【0】
Define the unit of PLC running time.
0: Second 1: Minute
F9.11 PLC step1 duration (T1) Range: 0.1~3600【20.0】