NE200/300 Series Drive User Manual
178 Chapter 6 Parameter description
0: RS485 Disabled
1: RS485 Enabled
Fd.01 Local address Range12471
Define the drive’s communicating address. The address set to 0 is for
the broadcast address to realize the PC broadcasting; when the drive
address is 247, it will serve as the host on the network to broadcast to other
slave machines to achieve synchronization function.
Note:
1) Local address should be the unique one; it is the foundation to realize
point-to-point communication between the host and drive.
2) When the drive is set to be host, the broadcasting interval is the
response delay time defined in Fd.05. If the response delay time is set
to be too short, the communication networking might get abnormal.
Fd.02 Baud rate Range: 053
Select the baud rate of serial communication. The master and the slave
must keep the same baud rate setting. Otherwise, they cannot
communicate normally. Higher baud rate could have a faster
communication.
0: 1200bpS
1: 2400bpS
2: 4800bpS
3: 9600bpS
4: 19200bpS
5: 38400bpS
Fd.03 Parity bit setup Range: 020