FP.02 Parameter initialization Range: 0~2【0】
0: No operation
1: Clear fault history
When FP.02 is set to 1, the fault records of FF.00~FF.07 will be
cleared.
2: Restore to default setting
When FP.02 is set to 2, the parameters (except running history and
user password) are restored to defaults.
FP.03 Parameter copy Range: 0~2【0】
0: No action
1: Parameters download
According to the type parameter of the keypad preservation (whether
has motor parameters, etc), automatically download to the control
board。
2: Parameters upload (except motor’s parameters)
All parameters will upload to EEPROM of keypad except “Running
history record” (Group FF) and “motor parameters” (Group F5).
3: Parameters upload (all parameters)
All parameters will upload to the EEPROM of keypad except “Running
history record” (Group FF).
FP.04 Parameter upload protection Range: 0~1【0】
0: Protection enabled
When the keypad has stored effective parameters, uploading
parameters to keypad is invalid and report “copy fault”
1: Protection disabled
No matter the panel has stored effective parameters or not, the
uploading operation will upload the present parameters from the
control board to the keypad panel.