NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 57
Code
Description Setting range Default Modify
Modbus
Address
control mode
2: Communication control
F0.03
Frequency
reference1
(Freq. ref.1)
0: Digital reference
(keypad, terminal
up/down)
0 ○ 0103H
1: Al1 2: Al2
3: PULSE setup
4: Communication
5:MS (Multi-step) Speed
6: PLC 7: PID
8: Keypad potentiometer
F0.04
Frequency
reference2
(Freq. ref.2)
1: Al1 2: Al2
1 ○ 0104H
3: PULSE setup
4: Communication
5:MS (Multi-step) Speed
6:
Reserved
7: Reserved
8: Keypad potentiometer
F0.05
Frequency
setting
selection
0:Freq. ref.1
0 ○ 0105H
1:Freq. ref.2
2: Freq. ref.1+ Freq. ref.2
3: Switch between Freq.
ref.1 & Freq. ref.2 by
terminal
4: Switch between (Freq.
ref.1+ Freq. ref.2) & Freq.
ref.1 by terminal
5:MIIN (Freq. ref.1, Freq.
ref.2)
6:MAX (Freq. ref.1, Freq.
ref.2)
F0.06
UP/DOWN
Preset freq.
0~ Max frequency 50.00Hz
○ 0106H
F0.07
Terminal UP/
DOWN rate
0.01~ 50.00Hz/s 1.00Hz/s
○ 0107H
F0.08
UP/DOWN 0: Keypad and terminal 1 ○ 0108H