SK 54xEUsers Manual for Frequency Inverters
70 BU 0505 EN-3021
Plug connector block X11 RS485 / RS232
Relevance
SK 540E SK 545E
Terminals X11:
1 2 3 4 5 6
RS485 A + RS485 A- GND 232 TXD 232 RXD +5V
Name
Contact Function
[factory setting]
Data Description / wiring suggestion Parameter
Note: Coupling of two frequency inverters via the RJ12 socket must only be made via the USS BUS (RS485). Care must be taken that
no connection to the data cable is possible via RS232, in order to prevent damage to this interface.
1
Data cable RS485
Baud rate
9600…38400 Baud
Terminal resistance
R=240 DIP 1 (see below)
RS485_A
RS485_B
GND
TXD
RXD
+ 5V
RJ12: Pin No. 1 … 6
P503
P509
2
3 Reference potential
for bus signals
(must always be
wired!)
0 V digital
4
Data cable RS232
Baud rate
9600…38400Baud
5
6 Internal 5V supply
voltage
5 V ± 20 %
optional
Adapter cable
RJ12 to SUB-D9
for RS232
communication
for direct connection
to a PC with NORD
CON
Length 3 m
Assignment of the SUB-D9
plug socket:
RXD
0V
TXD
6
1
5
9
TxD
RxT
GND
+ 5V
n.c.
n.c.
Part No. 278910240
DIP switch 1/2 (top side of frequency inverter)
DIP-1 Termination resistor for RS485 interface
(RJ12); ON = switched in
[Default = "OFF"]
For RS232 communication DIP1 to "OFF"
X11 X10 X9
RS485_A
RS485_B
GND
TXD
RX D
+ 5V
1 2
ON
CAN _H
CAN _L
CAN _G N D
nc
CAN _SH LD
CAN _G N D
nc
CAN_24V
CAN _H
CAN _L
CAN _G N D
nc
CAN _SH LD
CAN _G N D
nc
CAN_24V
RS232/485 DIP CAN/CANopen
DIP 2
Terminal resistor for CAN/CANopen interface
(RJ12); ON = switched in
[Default = "OFF"]