4 Commissioning
BU 0505 EN-3021 89
4.3 Minimal configuration of control connections
If the frequency inverter is to be controlled via the digital and analog inputs, this can be implemented
immediately in the condition as delivered. Settings are not necessary for the moment.
Minimum connections
Basic parameters
If the current setting of the frequency inverter is not known, loading the default setting is
recommended P523 = 1. The inverter is pre-programmed for standard applications in this
configuration. If necessary, the following parameters can be adjusted with the optional SimpleBox SK
CSX-0 or ControlBox TU3-CTR.
P5--
Additional
parameter
As standard, the actual
output frequency is displayed
P102
Acceleration time
0 ... 320s
Motor data
See 4.1 Default Settings
P400
Analog input function
0...10V frequency
Operating value display
(or operational)
following mains ON
P103
Deceleration time
0 ... 320s
P104
Min. frequency
0 ... 400Hz
P105
Max. frequency
0.1 ... 400Hz
P420
Digital input function 1
- ON right -
P523
=1
Load factory data
Pos: 117 /Anleitungen/ Elektronik/F U und Starter/4. Inbetriebna hme/SK 500E/4.3 KTY8 4-130 Anschluss (ab Soft ware Version 1.7) @ 0\mod_1327570 228346_388.doc x @ 7242 @ 255 @ 1
Potentiometer, 10kOhm
(Function P400 = 1)
(min./max. range = P104/105)
Switch, ON/OFF
(Function P420 = 1)
*Devices SK5x5E:
Terminal designation 44 instead of 42:
Size 1 - 4: 18V … 30V (according to input voltage VI)
Size 5 - 7: VO = 24V ± 25%
R = 10k
AIN 1
GND/0V
VO 10V
DIN 1
VO 15V
11
12
14
16
17
21
22
23
24
25
42
40
41