SK 54xE – Users Manual for Frequency Inverters
94 BU 0505 EN-3021
Operating displays
Abbreviations used:
• FI = Frequency inverter
• SW = Software version, stored in P707.
• S = Supervisor parameters are visible or hidden depending on P003.
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 123 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P000- P099/Parameter P000 – Betri ebsanzeige @ 0\mod_1327 573548773_388.doc x @ 7362 @ @ 1
P000
Operating display
(Operating parameter display)
0.01 ... 9999 In ParameterBoxes with 7-segment displays (e.g. SimpleBox) the operating value which is selected
in P001 is displayed online.
Important information about the operating status of the drive can be read out as required.
Pos: 124 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P000- P099/Parameter P001 – Aus wahl Anzeige @ 0\mod_132757372 8068_388.docx @ 7386 @ @ 1
P001
Display selection
(Display selection)
0 ... 65
{ 0 }
Selection of operating display of a parametrisation box with 7-segment display (e.g.: SimpleBox)
Currently supplied output frequency
Output frequency that corresponds to the pending setpoint. This
need not correspond with the current output frequency.
Current measured output current
Actual torque current [A]:
Torque-forming output current
Current alternating voltage present at the device output
The Link voltage [Vdc] is the FI-internal DC voltage. Amongst other
things, this depends on the level of the mains voltage.
Current calculated value of the power factor
8 =
Calculated current apparent power
Calculated current effective power
Calculated current torque
Calculated current field in motor
Time for which main voltage present at device
Operating time Enable [h]
"Enabled operating hours"
is the time for which the device was
enabled.
14 =
Current value that is present at analogue input 1 of the device
Current value that is present at analogue input 2 of the device
Heat sink temperature [°C]
Current temperature of the heat sink
Actual utilisation of motor
[%]
Average motor utilisation, based on the known motor data
(P201...P209).
Brake resistor utilisation
[%]
"Braking resistor utilisation" is the average braking resistor load,
based on the known resistance data (P556...P557).
Interior temperature [°C]
Current interior temperature of device
(SK 54xE / SK 2xxE)
Reserved
"Current motor potentiometer function setpoint with storage".
(P420…=71/72). The nominal value can be read out with this
function or pre-set (without the drive running).
Visualisation mode for PLC communication
Stator resistance determined by means of measurement (P220)