EasyManuals Logo

Notifier BACnet GW-3 User Manual

Notifier BACnet GW-3
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
BACnet GW-3 Configuration and Operation BACnet GW-3 Configuration
32 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Multiple Gateways
NFN networks with more than 15 nodes must be monitored using the Multiple Gateway
option.
When using this Multiple Gateway option, set the Multiple Gateway value to True, and enter a
value for each network node to be monitored by this BACnet GW-3.
You may enter up to 14 nodes for FACPs to be monitored, since the BACnet GW-3 can support
15 nodes including itself.
Apply Settings
Step 5. Once all BACnet GW-3 settings have been properly configured, click Apply at the bottom
of the Value pane to apply the settings and reboot the gateway.
NOTE: If you are changing settings on a BACnet GW-3 previously configured with monitored
nodes, this screen button will be labeled Apply And Delete Objects.