CHANGE ZONES - INCLUDE/EXCLUDE STATUS
An EXCLUDED Zone does not signal neither Alarms nor Troubles.
Use
CURSOR KEYS
to enter the zone number on which operate.
By pressing
ENTER
key, on the display appears the status of the zone
selected.
Press
ENTER
to modify the zone status.
If you do not want to change the zone status, press
ESC
.
»
NOTE: A)
PROGRAMMING THE CBE EQUATIONS
This function allows to map a set of events to each LOGIC ZONE (from the 13th one to the 20th), to activate it.
The admitted events are:
Alarm or Prealarm for initiating circuits (from 1 to 12);
Activated, for logic zones (from 13 to 20)
Maximum 4 events mapped to a logic zone can be programmed.
Each event is connected to the other by two types of conditions:
OR= it means either...or
AND= it means both...and
Example:
Follow this procedure to performe the programming:
Phase A)
Enter the zone number for which you wish to program the equation (13 to 20)
Now, enter 2 data: a zone number + its status (Alarm or Prealarm).
It is possible entering an operator of AND or OR with other zones and to continue the equation.
Page 10 Installation and Operating Manual CFP-600-Prog-3.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
INC./EXC.ZONES |A08
Z. __ |G08
|D00
|E00
INC./EXC. ZONES|A08
Z. 01 NORMAL |G08
|D00
Modify Exit |E00
Zone Status Detector Alarms Detector Troubles
Enabled YES YES
Disabled NO YES
Excluded NO NO
B) if a zone is EXCLUDED, any operation on it, is
inhibited (See config. Menu - Lev. 4 about
Exclusion function)
DESCRIPTION CHARACTERS TO BE PROGRAMMED
Result Zone nr. 20 active if... Z. 20
Event nr. 1 Zone nr. 1 in Alarm status 01 A
Condition or +
Event nr. 2 Zone nr. 2 in Pre-Alarm status 02 P
EQUATION
CONFIGURATION
EQUATION for Z. _ EQUATION for Z.2_ EQUATION for Z. 20