CHANGE ALARM TIME PARAMETER
This section shows the programmings of several times, supplied by the control panel.
Select the function from the menu by using
CURSOR
keys, and press
ENTER
The programming is carried out as the previous one, except that it is possible to enetr different figures according to the
time you are programming.
To enter the figures use
CURSOR
keys and press
ENTER
key to confirm.
* Note 1 - ALARM CONTROL: to program a duration time equal to INFINITE, that is to say til the RESET, enter: 00-00
»
NOTE: the above list shows the control panel factory-default times.
The same times are programmed in case of PROGRAMMING CLEARING
PROGRAMMING THE ALARM CONTROL MODULATION
This function allows to modify the relay operating frequency of: ALARM, PREALARM and SOUNDERS, when activated.
It is possible to achieve pause and activation times multiple of 1 second which may be programmed in cycles of 8 seconds
repetitive.
SOUND EXAMPLES:
Example Nr. 1= two 1-second beeps + one 3-second sound (repeated)
Example Nr. 2= 2-second beep (repeated)
Example Nr. 3= 3-second beep (repeated)
If the sequence programming is carried out entering a value equal to 1, a steady sound will be obtained (this is the factory-
default value).
The following controls may be programmed:
PREALARM
ALARM
SOUNDER
Use
CURSOR
keys to select the control, then press
ENTER
to modify it.
Use
CURSOR
keys to program 0/1 values, then press
ENTER
to confirm the programming.
The same as for the other functions, press
ESC
key to leave the function without changing the existing programming.
CFP-600-Prog-4.VP Installation and Operating Manual Page 15
Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
DEFAULT MIN MAX
30 seconds 1 second 09-59
2 minutes 0 seconds 19-59
30 seconds 0 seconds 19-59
20 minutes 20 minutes 99-59
Prealarm Time (Day mode)
Alarm Time (* Note 1)
Sounder Control Activation Time
Walk-Test and Line test max Time
0 1 0 1 0 111
01100 11 0
111 0 111 0
ALARM MODULAT. |A08
CONFIGURATION |G08
|D00
|E00
ALARM MODULAT. |A08
PREAL. SEQUENCE|G08