PROGRAMMING THE RELEASE ZONE MAPPING
This function allows to map TWO detecting zones or a single 2-threshold zone, to one of the two release channels, provi-
ded that the optional release board has been installed.
Use
CURSOR
keys to program each figure, then press
ENTER
to confirm. Press
ESC
to save.
CHANGE RELEASE TIME
This function allows to program timings concerning the release channel management.
Programming is valid for both the channels.
For further details see diagram on Appendix A (Release Time).
SELECT EVENT TYPE FOR HISTORICAL LOG
This function allows to select which of the following events store in the historical Log:
•
TROUBLES (Line and System Troubles)
•
RESET (control Panel Reset)
•
CONFIGURATION (Configuration Menu Access)
•
TEST MODE (Control Panel in Test Mode)
Press
ENTER
to have access into the Historical Log Functions.
The display shows the first function available.
Press
CURSOR
keys to select the desired function.
Press
ENTER
to change the programming.
Page 16 Installation and Operating Manual CFP-600-Prog-4.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
RELEASE ZONE |A08
CONFIGURATION |G08
|D00
|E00
RELEASE ZONE |A08
CHANNEL Nr. __ |G08
|D00
|E00
RELEASE ZONE |A08
CHANNEL Nr. 2 |G08
|D00
|E00
RELEASE ZONE |A08
CHANNEL Nr.2 |G08
Z. __ Z. __ |D00
|E00
DEFAULT MIN MAX
30-00 1 minute 59-59
00-30 5 seconds 4-59
00-05 00-00 19-59
00-30 10 4-59
•
2nd ALARM Waiting Time
•
EVACUATION Time
•
Release Actuation Time (0000 INFINITE)
•
Release Repetition (Waiting Time before repeating the release,
in case of negative result).
HISTORICAL LOG |A08
CONFIGURATION |G08
|D00
|E00
TROUBLE |A08
HISTORICAL LOG |G08
|D00
|E00
TROUBLE |A08
HISTORICAL LOG |G08
YES |D00