During these steps, it needs to follow some rules:
Use
CURSOR
keys to select the field to program.
Use
ENTER
key to go into the field and modify it.
If the cursor on the display is a blinking square, it means you are selecting a field.
If the cursor on the display is a blinking line, it means you are programming a field value.
While programming or modifying a field:
Use
CURSOR
keys to set a value for the character, in the cursor position.
Press
ENTER
to confirm the value.
As far as the zone number is concerned, after the second figure programming, it needs to press
ENTER
again to confirm the complete zone number.
Example:(after phase A):
›
Phase B) - program the Zone number:
›
Phase C) - Select the Zone status:
CHANGE SERVICE ENABLING STATUS
This section includes several enabling functions and services, supplied by the control panel.
Select the desired function by using
CURSOR
keys, then press
ENTER
.
In this example is showed only how to modify the first function, as for the other ones, the procedure is exactly the same.
Press
ENTER
to ENABLE and DISABLE the function.
If you DO NOT WANT to modify, press
ESC
.
CFP-600-Prog-3.VP Installation and Operating Manual Page 11
Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
EQUATION for Z. 20
EQUATION for Z.20
1
EQUATION for Z. 20
12
EQUATION for Z. 20
12A
EQUATION for Z.20
12P
Now:
- press ESC to accomplish the equation
- press UPWARDS CURSOR Key to go on.
EQUATION for Z. 20
12P+
Select an operator (+ means OR, * means AND) by using CURSOR keys.
After confirming with ENTER, repeat the procedure starting from phase B.
•
Initiating circuit for Remote Reset
•
Initiating circuit for Remote Signal Silence
•
Mains Trouble Signal
•
Battery trouble Signal
•
Power Supply Trouble Enabling
•
Sounder Trouble Enabling
•
16-relay board Installation
•
Release board Installation
•
Enabling operation of Manual release 1
•
Enabling operation of Manual release 2
REMOTE RESET |A08
ENABLING |G08
YES |D00
|E00
REMOTE RESET |A08
ENABLING |G08
YES |D00
Modify Exit |E00
REMOTE RESET |A08
ENABLING |G08
NO |D00
Modify Exit |E00