PROGRAMMING THE RELAY MAPPING (on optional 16-relay board)
This function allows to map each zone (1-20, 12 lines + 8 logic zones) to a control of those available on the optional 16-re-
lay board.
Press
ENTER
to have access to the function.
By using
CURSOR
key, enter the ZONE number.
Press
ENTER
to confirm.
By using
CURSOR
key, enter the RELAY number.
Press
ENTER
to confirm.
»
NOTE: by entering the relay number equals to 0, it means that no relay will be mapped.
In addition, it is possible to map the same control relay to more zones, obtaining the OR function of the zone.
ENABLING THE RELAY SIGNAL SILENCE (on optional 16-relay board)
This function allows to enable the signal silence of each control relay.
Press
ENTER
Use
CURSOR
keys to select the relay number to be changed.
Press
ENTER
to confirm
.
Press
ENTER
to enable and disable the signal silence.
CFP-600-Prog-3.VP Installation and Operating Manual Page 13
Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
RELAY MAPPING | A00
CONFIGURATION | G00
| D00
| E00
RELAY MAPPING | A00
Z. 01 | G00
0 02 | D00
| E00
RELAY MAPPING | A00
Z.01 | G00
| D00
| E00
IMPORTANT NOTE: CONTROL PANEL ZONES
During the programming 20 ZONES are available.
And exactly:
The first 12 zones are the line initiating circuits (DETECTOR ZONES)
Zones 13 to 20 are LOGIC ZONES which can be used to program the actions to carry
out in case of Alarm or Prealarm condition.
RELAY PROGR. | A00
CONFIGURATION | G00
| D00
| E00
R. __ | A00
| G00
| D00
| E00
R. 02 |A08
SILENCEABLE |G08
YES |D00
Modify Exit |E00